HY-ALERTA™ 2620 Explosion Proof Area Hydrogen Monitor

H2scan's 2620 Explosion Proof Area Hydrogen Monitor provides hydrogen-specific leak detection and measurement for hydrogen concentrations as low as 4000 ppm and can be scaled to any concentration up to 5% hydrogen by volume, a range representing 10% to 125% of hydrogen's low flammability limit. The monitor is designed for either ceiling or wall mount. H2scan's hydrogen-specific sensor technology has no cross sensitivity to other combustible gases, thus eliminating false positive alarms and ensuring safety system reliability.
HY-ALERTA-2620
HY-ALERTA-2620

Performance:
  • Hydrogen Sensitivity Range: 0.4% to 5.0% hydrogen by volume, 10% to 125% hydrogen lower flammable limit
  • Response Time: T90 < 60 sec
  • Ingress Protection: IP64 capable
  • Calibration Interval: 90 days
  • Product Life Expectancy: 10 years
  • Accuracy: ± (3% of reading + 0.2) percent hydrogen by volume

Interface Options:
  • Input Voltage Range: 90 VAC to 240 VAC
  • Input Power: 15W
  • Analog Outputs:
    Output Currents
    - 4 mA to 20 mA
    - 0 mA to 20 mA
    - User-specific mA range
  • Serial Communication Options: RS232 or RS422
  • Relay Contacts: Two programmable relays and one fault relay with both normally open (N.O.) and normally closed (N.C.) contacts:
    - 5A/240VAC
    - 5A/ 30 VDC

Dimensions:
  • Width: 13.8 cm (5.4 in)
  • Length: 19.2 cm (7.5 in)
  • Depth: 13.0 cm (5.7 in)

Operating Conditions:
  • Operating Temperature Range: -20șC to 55șC
  • Storage Temperature Range: -30șC to 80șC
  • Operating Humidity: 0% to 95% RH (non-condensing)
  • Calibration Background Gas: Air